Skip to content

Flowline Switch-Tek LU10 Ultrasonic Point Level Switch

Flowline Switch-Tek LU10 Ultrasonic Point Level Switch

Flowline Switch-Tek LU10 Ultrasonic Point Level Switch

The Flowline Switch-Tek™ LU10 is a compact ultrasonic gap switch. It handles high- or low-level alarm and control in chemical and low-viscosity liquids. A pair of piezo elements across a small gap detect whether liquid is present, with ±0.5 mm repeatability. A 60 VA SPST relay drives a PLC or one of Flowline’s Switch-Pro relay controllers. The relay is set normally open or normally closed simply by the polarity of the supply wiring. There are no moving parts, so it is unaffected by the density and specific-gravity issues that limit float switches.

The sensor and cable are moulded in polypropylene (IP68) or PFA (IP65). That suits aggressive media such as hydrochloric acid, sulphuric acid and diesel. The 3/4″ NPT (or G/R) body mounts through the tank wall in any orientation. It can also mount inside the tank on Flowline’s Smart Trak and Switch-Pak fittings. Short and long sensor lengths are available. It is rated 10 bar at 25 °C and −40 to 80 °C. Jadler Industries stocks the LU10 in Calgary for chemical-feed tanks, IBCs and sumps across Western Canada.

Flowline Switch-Tek LU10 Ultrasonic Point Level Switch
  • Features & Benefits
  • Applications
  • Product manuals
  • Product specs
  • No moving parts — unaffected by liquid density or specific gravity
  • Submersible PP or PFA sensor and cable for corrosive liquids
  • 60 VA SPST relay, selectable NO or NC via supply wiring polarity
  • ±1 mm accuracy and ±0.5 mm repeatability in water
  • Universal mounting through the tank wall or inside the tank
  • Compatible with Smart Trak and Switch-Pak installation fittings
  • Short and long sensor lengths
  • Ideal as a high or low level switch (per Flowline)
  • High or low level detection in chemical and low-viscosity liquids
  • Hydrochloric acid, sulphuric acid and diesel fuel tanks
  • IBCs, drums, skids and machines
  • Neutralization tanks and wastewater sumps
  • Pump, valve or alarm automation via a Switch-Pro controller
OrientationUniversal
Accuracy / repeatability±1 mm / ±0.5 mm in water
Supply12–36 V DC, 25 mA maximum
Contact1 × SPST relay, 60 VA, selectable NO / NC
Process temperature−40 to 80 °C (−40 to 176 °F)
Pressure150 psi (10 bar) at 25 °C, derated 1.667 psi per °C above 25 °C
Sensor rating / materialPP: NEMA 6 (IP68); PFA: NEMA 4X (IP65)
Cable4-conductor shielded 22 AWG, 10 ft (3 m); 25 ft and 50 ft to order
Process mount3/4″ NPT (3/4″ G / R); Viton gasket
Sensor lengthShort or long
ComplianceCE, RoHS
Download full spec sheet (PDF)

Request a quote

For: Flowline Switch-Tek LU10 Ultrasonic Point Level Switch. Tell us your application and quantity. Prefer to talk? Call 403-275-3601.