Skip to content

Flowline EchoPod UG01 / UG03 Ultrasonic Level Transmitter

Flowline EchoPod UG01 / UG03 Ultrasonic Level Transmitter

Flowline EchoPod UG01 / UG03 Ultrasonic Level Transmitter

The Flowline EchoPod® UG01 and UG03 are small non-contact ultrasonic level transmitters. They suit tanks up to 1.5 m and 3 m deep. Each combines a two-wire 4-20 mA level output with four SPST relays that run Flowline’s embedded control logic. The logic can run a single pump or valve with three alarms. It can also run two-pump lead-lag or duplexing with two alarms, or four independent switch points. The whole package screws into a 2″ NPT or G fitting. It has a polypropylene IP68 enclosure and a PVDF transducer for chemical duty.

What sets the UG series apart is Flowline’s Reflective Technology. The transducer is mounted vertically and fires off a 45° reflector. Condensation runs off instead of pooling on the face and attenuating the echo. That is the usual failure mode of ultrasonic sensors in humid or vapour-laden tanks. A narrow 2″ beam and short dead band suit day tanks, IBCs and drums. Everything is configured over USB with Flowline’s free WebCal software via the optional LI99-2001 Fob. Jadler Industries stocks the EchoPod in Calgary for chemical-feed and small-tank level control across Western Canada.

Flowline EchoPod UG01 / UG03 Ultrasonic Level Transmitter
  • Features & Benefits
  • Applications
  • Product manuals
  • Product specs
  • 1.5 m (UG01) and 3 m (UG03) ranges for small tanks
  • 4-20 mA output plus four programmable relays with embedded level-control logic
  • Reflective Technology for reliable measurement in condensing environments
  • Narrow 2″ beam for applications with limited space
  • Short dead band (1.5″ on UG01) maximizes tank filling capacity
  • Corrosion-resistant PVDF transducer and compact PP enclosure
  • Automatic temperature compensation from −40 to 80 °C
  • Fail-safe diagnostics with selectable relay and signal outputs
  • Day tanks, IBCs and drums
  • Cooling towers, skids and machines
  • Process tanks and waste sumps
  • Chemical, water, wastewater and oil in small tanks with non-foaming, mildly vaporous media
  • Pump and valve control and alarms via the four relays
RangeUG01: 1.5″ to 4.9 ft (3.8 cm to 1.5 m); UG03: 4″ to 9.8 ft (10.1 cm to 3 m)
Accuracy / resolutionUG01: 0.125″ (3 mm) / 0.5 mm; UG03: ±0.2% of range / 1 mm
Dead band / beam widthUG01: 1.5″ (3.8 cm); UG03: 4″ (10.1 cm) / 2″ (5 cm)
Signal output4-20 mA two-wire, invertible, selectable fail-safe; 500 Ω loop at 24 V DC
Relays4 × SPST, 60 VA, 1 A max.; selectable fail-safe and hysteresis
Supply14–28 V DC, max. 0.5 W
ConfigurationWebCal PC software over USB 2.0 (LI99-2001 Fob); non-volatile memory
Process / ambient temperature−40 to 80 °C process; −35 to 60 °C ambient; automatic compensation
Pressure30 psi (2 bar)
Enclosure / materialsType 6P (IP68); polypropylene enclosure, PVDF reflective transducer, polyurethane cable jacket
Cable / mount9-conductor shielded, 48″ (1.2 m); 2″ NPT or 2″ G
Classification / complianceGeneral purpose; UL 61010-1; CE, RoHS
Download full spec sheet (PDF)